Following the Code

Following the Code

Code changes are an important part of access control or egress

Although the code language has been refined over the last few editions of both the International Building Code (IBC) and NFPA 101—The Life Safety Code—the code requirements for electrified hardware continue to be confusing, often resulting in inconsistent application and enforcement.

There are seven basic code categories for electrified hardware used to control access or egress, and each has seen recent code changes. Many of these code applications, but not all, fall into the category commonly called “special locking arrangements.” We’ll review all seven categories, providing code references to facilitate additional research and highlighting the relevant changes that integrators need to be aware of to avoid costly and potentially dangerous violations.

Controlled Access / Free Egress: IBC – 1010.1.9 (2015), 1008.1.9 (2012); NFPA 101 – 7.2.1.5 (2015 and 2012)

The majority of electrified hardware applications fall into this category. As the name implies, an access control reader does not inhibit egress, it controls access only and is typically mounted on the ingress side of the opening.

This type of system is not addressed by the codes as a special locking arrangement, because the hardware allows free egress by turning the lever on the lockset or pushing the touchpad on the panic hardware. The same code requirements that apply to mechanical hardware must be met by doors with this type of electrified hardware. Doors must be readily operable from the egress side without keys, tools, or special knowledge or effort, and without tight grasping, tight pinching, or twisting of the wrist. One operation must unlatch the door from the egress side, and operable hardware must be mounted between 34 inches and 48 inches above the floor. Applications that do not allow immediate free egress will typically fall into one of the categories outlined below.

Delayed Egress: IBC – 1010.1.9.7 (2015), 1008.1.9.7 (2012); NFPA 101 – 7.2.1.6.1 (2015 and 2012)

Delayed egress locking systems may include panic hardware or an electromagnetic lock with delayed egress circuitry, or a delayed egress controller used in combination with other listed components. This hardware delays entrance or exit for no more than 15 seconds unless a 30-second delay is approved by the Authority Having Jurisdiction (AHJ). The use of these locks is dependent upon the use group or occupancy classification, and the requirements vary between the IBC and NFPA 101. The IBC does not allow delayed egress locks on Assembly, Educational, or High Hazard occupancies; NFPA 101 includes limitations specific to each occupancy classification.

There are many conditions for the use of delayed egress locks, including a sprinkler/fire alarm system that releases the lock to allow immediate egress upon activation. Actuation requirements to begin the 15-second timer now include a maximum force of 15 pounds applied for no more than 3 seconds, making it consistent with NFPA 101 requirements. The 2015 edition of the IBC also added a requirement for delayed egress locks to be listed in accordance with UL 294: Access Control System Units.

Controlled Egress: IBC – 1010.1.9.6 (2015), 1008.1.9.6 (2012); NFPA 101 – 18.2.2.2.5-6, 19.2.2.2.5-6 (2015 and 2012)

This application is specific to healthcare occupancies equipped throughout with an automatic sprinkler system or automatic smoke or heat detection system, and allows certain types of units to have locked doors in a means of egress when this control is needed for the safety or security of the patients.

Electromagnetic locks, or delayed egress devices modified to have an “infinite delay” instead of the typical 15-second delay are the most common locks used in a controlled egress system. Both of these products must be fail safe and allow free egress when power is removed. The 2009 IBC incorrectly referred to the products used in these systems as “delayed egress locks” even though this section of the code does not require the hardware to release automatically after a timer is actuated. This terminology was changed to “special egress” in the 2012 edition, and is now called “controlled egress” in the 2015 edition.

The IBC states that a building occupant must not be required to pass through more than one door with a controlled egress lock before reaching an exit, and emergency lighting is required at the door. The 2015 IBC has added a requirement for the locking system to be listed in accordance with UL 294, but the NFPA 101 requirements vary slightly, so refer to the referenced section for specifics.

Electromagnetic Lock with Sensor Release: IBC – 1010.1.9.8 (2015), 1008.1.9.8 (2012); NFPA 101 – 7.2.1.6.2 (2015 and 2012)

'In recent editions of the IBC and NFPA 101, the section that applies to locks released by a sensor is called Access Controlled Egress Doors. Because of this title, this section was sometimes misapplied to all doors with access control readers, even though those most of those doors typically allow free egress without sensors or other release devices. In the 2015 IBC, the title of the section was changed to Sensor Release of Electrically Locked Egress Doors, to avoid this confusion.

'This section is typically applied to electromagnetic locks, and mag-locks that are unlocked by door-mounted hardware instead of a sensor are addressed by a different set of code requirements. A mag-lock that is released by a sensor detecting an approaching occupant is also required to be released by actuation of a marked push button adjacent to the door, and by activation of the fire alarm or sprinkler system (if present), and upon power failure.

Electromagnetic Lock with Door Hardware Release: IBC – 1010.1.9.9 (2015), 1008.1.9.9 (2012); NFPA 101 – 7.2.1.5.6 (2015 and 2012)

In the 2009 editions of both the IBC and NFPA 101, a new section was added to address doors with mag-locks that are released by hardware mounted on the door. The door-mounted hardware may include a lever handle, panic hardware, or other device equipped with a request-to-exit (REX or RX) switch or an electronic touch sensor. The added section clarifies the code requirements for mag-locks released this way as opposed to mag-locks released by a sensor.

A mag-lock released by door-mounted hardware may not be used in all use group or occupancy types, so refer to the applicable code to verify the acceptable locations. The door must be equipped with listed hardware mounted on the door leaf, which incorporates a built-in switch to directly release the electromagnetic lock and unlock the door immediately. The release device must have an obvious method of operation, and must be readily operated with one hand under all lighting conditions. The code requirements that address this application do not require the lock to unlock upon actuation of the fire alarm or sprinkler system, but the lock must unlock upon loss of power to the switch in the door-mounted hardware.

Elevator Lobby Egress: IBC – 3006.4 (2015), 713.14.1 (2012); NFPA 101 – 7.2.1.6.3 (2015 and 2012)

The IBC does not currently include a section specific to locks on elevator lobby doors; elevator lobbies are required to have a code-compliant means of egress, so methods used to secure the doors would be limited by the IBC to an alarm to discourage egress through the tenant space, or possibly a delayed egress lock. For facilities where NFPA 101 (2009 edition or later) is enforced, a fail-safe lock may be used if other criteria are met. This lock will allow access through the secured doors during a fire alarm, so building occupants can find another exit. Note that some jurisdictions have adopted modifications to the IBC that address locks on elevator lobby doors.

NFPA 101 permits electrified locking of elevator lobby doors only if the building has an automatic sprinkler system or a fire alarm system and where this type of locking is allowed by the occupancy chapters. The lock must unlock automatically upon actuation of the sprinkler system or fire alarm system (except when the system is initiated by a manual fire alarm box) and upon loss of power to the lock. When the lock is unlocked, the doors must remain unlocked until the fire alarm system has been manually reset. If the locking hardware has a latch, there must be code-compliant hardware on the door leaf to release the latch. Locking systems used on elevator lobby doors must be listed in accordance with UL 294, and a two-way communication system must be installed in the elevator lobby to allow a building occupant to call for help.

Stairwell Reentry: IBC – 1010.1.9.11 and 403.5.3 (2015), 1008.1.9.11 and 403.5.3 (2012); NFPA 101 – 7.2.1.5.8 (2015 and 2012)

If stair doors are locked on the stair side, they must allow reentry back into the building to ensure the safety of building occupants during a fire. If a stairwell becomes compromised by smoke, occupants are able to leave the stair through remotely-unlocked doors and find another exit.

A fail safe lockset or fail safe lever trim for fire exit hardware is typically used to meet the stairwell reentry requirements. Electric strikes may not be used for stairwell reentry because electric strikes on fire doors must be fail secure. If an electromagnetic lock is used on a stair door in order to unlock the door remotely, latching hardware must also be present in order to provide the positive latching required for fire doors.

When considering which code requirements to follow, first identify which category the hardware falls into, and refer to the applicable code section. Keep in mind that state or local requirements could differ from those of the IBC or NFPA 101, so it’s important to be aware of the codes in your facility’s jurisdiction. Refer to the published codes for the detailed code requirements, and consult the Authority Having Jurisdiction for more information about local requirements.

This article originally appeared in the April 2016 issue of Security Today.

Featured

  • Gaining a Competitive Edge

    Ask most companies about their future technology plans and the answers will most likely include AI. Then ask how they plan to deploy it, and that is where the responses may start to vary. Every company has unique surveillance requirements that are based on market focus, scale, scope, risk tolerance, geographic area and, of course, budget. Those factors all play a role in deciding how to configure a surveillance system, and how to effectively implement technologies like AI. Read Now

  • 6 Ways Security Awareness Training Empowers Human Risk Management

    Organizations are realizing that their greatest vulnerability often comes from within – their own people. Human error remains a significant factor in cybersecurity breaches, making it imperative for organizations to address human risk effectively. As a result, security awareness training (SAT) has emerged as a cornerstone in this endeavor because it offers a multifaceted approach to managing human risk. Read Now

  • The Stage is Set

    The security industry spans the entire globe, with manufacturers, developers and suppliers on every continent (well, almost—sorry, Antarctica). That means when regulations pop up in one area, they often have a ripple effect that impacts the entire supply chain. Recent data privacy regulations like GDPR in Europe and CPRA in California made waves when they first went into effect, forcing businesses to change the way they approach data collection and storage to continue operating in those markets. Even highly specific regulations like the U.S.’s National Defense Authorization Act (NDAA) can have international reverberations – and this growing volume of legislation has continued to affect global supply chains in a variety of different ways. Read Now

  • Access Control Technology

    As we move swiftly toward the end of 2024, the security industry is looking at the trends in play, what might be on the horizon, and how they will impact business opportunities and projections. Read Now

Featured Cybersecurity

Webinars

New Products

  • A8V MIND

    A8V MIND

    Hexagon’s Geosystems presents a portable version of its Accur8vision detection system. A rugged all-in-one solution, the A8V MIND (Mobile Intrusion Detection) is designed to provide flexible protection of critical outdoor infrastructure and objects. Hexagon’s Accur8vision is a volumetric detection system that employs LiDAR technology to safeguard entire areas. Whenever it detects movement in a specified zone, it automatically differentiates a threat from a nonthreat, and immediately notifies security staff if necessary. Person detection is carried out within a radius of 80 meters from this device. Connected remotely via a portable computer device, it enables remote surveillance and does not depend on security staff patrolling the area. 3

  • FEP GameChanger

    FEP GameChanger

    Paige Datacom Solutions Introduces Important and Innovative Cabling Products GameChanger Cable, a proven and patented solution that significantly exceeds the reach of traditional category cable will now have a FEP/FEP construction. 3

  • Mobile Safe Shield

    Mobile Safe Shield

    SafeWood Designs, Inc., a manufacturer of patented bullet resistant products, is excited to announce the launch of the Mobile Safe Shield. The Mobile Safe Shield is a moveable bullet resistant shield that provides protection in the event of an assailant and supplies cover in the event of an active shooter. With a heavy-duty steel frame, quality castor wheels, and bullet resistant core, the Mobile Safe Shield is a perfect addition to any guard station, security desks, courthouses, police stations, schools, office spaces and more. The Mobile Safe Shield is incredibly customizable. Bullet resistant materials are available in UL 752 Levels 1 through 8 and include glass, white board, tack board, veneer, and plastic laminate. Flexibility in bullet resistant materials allows for the Mobile Safe Shield to blend more with current interior décor for a seamless design aesthetic. Optional custom paint colors are also available for the steel frame. 3