Sophisticated and Strategic

To protect information assets, a fire protection strategy must incorporate specific emergency identification and suppression alongside detection

Mission-critical facilities such as data and telecommunications centers must maintain operations without interruption. Mission continuity is ensured for facilities through the use of redundant power supplies and mechanical systems and cuttingedge fire protection systems.

Fire in these facilities obviously can threaten the business and human life. Key to defending against a catastrophe is a sophisticated fire protection system that integrates seamlessly with the entire environment.

Fire protection for mission-critical facilities can be complex and daunting. System designs should be based on a total fire protection approach in which three conditions are met: identifying the presence of a fire, communicating the existence of that fire to the occupants and proper authorities, and containing and extinguishing the fire, if possible. Being familiar with all technologies associated with fire detection, alarming and suppression is important to developing a sound fire protection solution.

Fire Detection Strategies

There are many ways of detecting and suppressing fires, but only a few should be used for mission-critical applications. For example, the main goal of the fire protection system in a data center is to get the fire under control without disrupting the flow of business or threatening occupants.

Spot Detection

For the purposes of protecting a mission-critical facility, addressable early-warning smoke detectors and heat detectors can be an option. Because the airflows are rapid in an area such as a data center, it is important to realize the differences between types of detectors.

Ionization smoke detectors are quicker at detecting flaming fires, such as those commonly found in chemical storage areas, rather than slow, smoldering fires that most typically occur in data centers and telecom equipment spaces. Ionization sensors almost immediately recognize fires characterized by combustion particles from 0.01 to 0.3 microns. However, ionization sensors offer limited or slower capabilities when installed in areas with high airflow, which is often the case in mission-critical environments.

Photoelectric smoke detectors, however, quickly respond to smoldering fires characterized by combustion particles from 0.3 to 10.0 microns, making these detectors more appropriate for most mission-critical settings.

One solution for detecting a broad range of fires quickly would be a multicriteria detector that uses photoelectric particulate detection in tandem with sensors that detect other products of combustion, such as carbon monoxide (CO) and light (infrared). Together, these signals are cross-referenced by an onboard microprocessor that uses algorithms to “process out” false alarms while enhancing the response time to real fires.

Another solution is to use intelligent high-sensitivity detectors, which are very similar to standard detectors except that they employ a more highly advanced detection method.

High-sensitivity spot detection typically employs a focused laser-based source to achieve sensitivities that are 100 times more sensitive than standard addressable or conventional infraredbased photoelectric smoke detectors. They are designed to respond to incipient fire conditions as low as 0.02 percent per foot obscuration to provide valuable time for staff to investigate the affected area and take appropriate action to mitigate risk.

These detectors are addressable and able to send information to the central control station, thereby pinpointing the exact location of the smoke. Some can automatically compensate for changes in the environment, such as humidity and dirt buildup. They also can be programmed to be more sensitive during certain times of the day. For instance, when workers leave the area, sensitivity will increase.

High-sensitivity detectors are commonly placed below raised floors, on ceilings and above drop-down ceilings, as well as in air-handling ducts to detect possible fires within the HVAC system.

Aspirating Smoke Detection

Many air-sampling smoke detectors also can provide high-sensitivity detection. Some systems can be up to 1,000 times more sensitive than a standard photoelectric or ionization smoke detector and are capable of detecting byproducts of combustion in concentrations as low as 0.00046 percent per foot obscuration. This type of detection provides advanced notification so facility managers or other appropriate staff can intervene and take action before a combustion event becomes disastrous.

An aspiration system works by drawing in smoke through a network of piping via the aspirator (fan). The air sample is then passed through a filter and into the sensing chamber of the detector. Using advanced sensing technology, the detector analyzes the air sample and sends a signal of airborne smoke intensity to a remote or integrated display module and a fire detection panel, when necessary, to raise an alarm.

These detectors communicate information to a fire alarm control panel, a software management system or a building management system through relays or another interface. With some systems, email updates can be sent to appropriate staff to communicate alarm levels, urgent or minor faults or other status conditions via relays. The multiple warning levels of this system can trigger different responses at different stages of a fire, from controlling air conditioning to suppression release. To accommodate specific codes or environments, alarm relays can be set with 0- to 60-second delays.

Fire Suppression Systems

Although smoke detectors primarily alert of a fire condition, in a missioncritical facility they may also be used to control the release of fire suppression systems. Should a fire occur, suppression systems are the next line of protection and can quickly extinguish the fire with minimal or no effect on the operation. It is important to consider the suppression system to be used.

Sprinkler Systems

Sprinkler systems, which are designed specifically for protecting the structure of the building, can be installed in four different configurations: wet-pipe, drypipe, deluge and pre-action. The wetpipe system consists of a piping system connected to a water source and filled with water so that water discharges immediately from sprinklers activated by a fire. In general, wet-pipe sprinklers are not recommended for mission-critical facilities; however, depending on local fire codes, they may be required.

A dry-pipe system is typically used in areas subject to freezing and consists of piping connected to a water source and filled with air pressure supplied by a compressor. When a sprinkler is activated, the air is expelled first, allowing a special check valve, called a dry-pipe valve, to operate. This allows water to flow into the piping and out any open sprinklers. This, too, is not ideal for mission-critical facilities.

A pre-action system is more common in a mission-critical facility. “A pre-action sprinkler system is one effective alternative because of its dualaction criteria,” said Ramzi Namek, director of engineering for Total Site Solutions, Columbia, Md. “The pipe remains dry until the fire detection system activates a control valve (located outside the data center to avoid damage from leaks), filling it with water.”

It consists of closed-type sprinkler heads connected to a series of piping arrangements. The system has a preaction valve that prevents the pipes from filling with water during normal times. This valve is held closed electrically by activation of the detection system (fire detectors) being released only when an electrical signal is sent to the releasing solenoid valve. Upon receipt of the signal, which could be from any of the sensors attached to the system, an electrical mechanism opens the pre-action valve, and the pipelines fill with water under pressure. The system at that point functions as a standard wet-pipe system. The water tanks are located away from the area but are readily accessible.

“Another important design consideration to plan for is space for suppressionagent tanks. Some suppression agents are stored in gas form; others are stored as a liquid, which can impact the number and size of tanks required,” explains Namek.

Clean-agent Suppression

In addition to sprinkler systems, cleanagent suppression systems can extinguish fires in their incipient stage, well before enough heat builds in a room to activate a sprinkler system. When activated, these waterless flame-suppression systems discharge as a gas. The gas reaches all areas of the protected facility and leaves no residue to damage sensitive equipment or require costly cleanup. Clean agents suppress fires by many methods, including depleting the area of oxygen, interrupting the chemical reactions occurring during combustion, and absorbing heat.

“Clean-agent systems typically use [3M] Novec 123, [DuPont] FM-20, or [Ansul] Inergen. They combine the benefits of clean-agent systems and active fire protection with people-safe, clean, environmentally friendly performance,” said Eric Fournier, project manager at Total Site Solutions.

Clean-agent suppression systems, protecting both the areas underneath and above the raised floor, are the most common method of fire protection for Class C electrical hazards. “Raised floors bring up some important issues with regard to fire protection in mission- critical facilities,” said Fournier. Spaces beneath raised floors often experience many air changes per hour, which presents a difficult detection design.

“Because raised floors create a completely separate plenum and pose as much of a fire hazard as the numerous pieces of computer equipment situated on the raised floors,” Fournier said, “they must be protected with the same level of fire protection as the space above.”

These clean-agent suppression systems, when controlled by an interface with a high-sensitivity smoke detection system, suppress fires without damaging IT equipment and allow staff to get the facility up and running faster.

Regardless of which detectors or systems are used in the fire and life safety design in a mission-critical facility, all must be networked into one central location. Whether that is a series of panels or a control center, there will be a vast amount of equipment used—hundreds and maybe thousands of devices, depending upon the size of the facility. Programming is the key to how well all the pieces come together. The outcome for a fire and life safety system within a missioncritical system remains to minimize or prevent a fire event in order to maintain constant operation and protect occupants.

This article originally appeared in the March 2012 issue of Security Today.

Featured

  • Report Shows Cybercriminals Continue Pivot to Stealthier Tactics

    IBM recently released the 2025 X-Force Threat Intelligence Index highlighting that cybercriminals continued to pivot to stealthier tactics, with lower-profile credential theft spiking, while ransomware attacks on enterprises declined. IBM X-Force observed an 84% increase in emails delivering infostealers in 2024 compared to the prior year, a method threat actors relied heavily on to scale identity attacks. Read Now

  • 2025 Security LeadHER Conference Program Announced

    ASIS International and the Security Industry Association (SIA) – the leading membership associations for the security industry – have announced details for the 2025 Security LeadHER conference, a special event dedicated to advancing, connecting and empowering women in the security profession. The third annual Security LeadHER conference will be held Monday, June 9 – Tuesday, June 10, 2025, at the Detroit Marriott Renaissance Center in Detroit, Michigan. This carefully crafted program represents a comprehensive professional development opportunity for women in security this year. To view the full lineup at this year’s event, please visit securityleadher.org. Read Now

    • Industry Events
  • Report: 82 Percent of Phishing Emails Used AI

    KnowBe4, the world-renowned cybersecurity platform that comprehensively addresses human risk management, today launched its Phishing Threat Trend Report, detailing key trends, new data, and threat intelligence insights surrounding phishing threats targeting organizations at the start of 2025. Read Now

  • NRF Supports Federal Bill to Thwart Retail Crime

    The National Retail Federation recently announced its support for the Combating Organized Retail Crime Act of 2025. The act was introduced by Chairman Chuck Grassley, R-Iowa, Senator Catherine Cortez Masto, D-Nev., and Representative Dave Joyce, R-Ohio. Read Now

  • ISC West 2025 Brings Almost 29,000 Industry Professionals to Las Vegas

    ISC West 2025, organized by RX and in collaboration with the Security Industry Association, concluded at the Venetian Expo in Las Vegas last week. The nation’s leading comprehensive and converged security event attracted nearly 29,000 industry professionals and left a lasting impression on the global security community. Over five action-packed days, ISC West welcomed more than 19,000 attendees and featured 750 exhibiting brands. Read Now

    • Industry Events
    • ISC West

New Products

  • FEP GameChanger

    FEP GameChanger

    Paige Datacom Solutions Introduces Important and Innovative Cabling Products GameChanger Cable, a proven and patented solution that significantly exceeds the reach of traditional category cable will now have a FEP/FEP construction.

  • A8V MIND

    A8V MIND

    Hexagon’s Geosystems presents a portable version of its Accur8vision detection system. A rugged all-in-one solution, the A8V MIND (Mobile Intrusion Detection) is designed to provide flexible protection of critical outdoor infrastructure and objects. Hexagon’s Accur8vision is a volumetric detection system that employs LiDAR technology to safeguard entire areas. Whenever it detects movement in a specified zone, it automatically differentiates a threat from a nonthreat, and immediately notifies security staff if necessary. Person detection is carried out within a radius of 80 meters from this device. Connected remotely via a portable computer device, it enables remote surveillance and does not depend on security staff patrolling the area.

  • Automatic Systems V07

    Automatic Systems V07

    Automatic Systems, an industry-leading manufacturer of pedestrian and vehicle secure entrance control access systems, is pleased to announce the release of its groundbreaking V07 software. The V07 software update is designed specifically to address cybersecurity concerns and will ensure the integrity and confidentiality of Automatic Systems applications. With the new V07 software, updates will be delivered by means of an encrypted file.